Chapter 3: Power Generators & Load Curves

Power generator sets (portable generators and trailer-mounted power units) are the backbone of any temporary grid – from portable 5 kVA inverter units to trailer-mounted 200 kVA generators.


⚡ Adding Generators & Unit Presets

Tap Generators in the menu and then tap the round button “+ Add Generator”. You can either select a predefined equipment preset or enter custom parameters:

Standard Equipment Presets in the Catalog:

Generator Preset Typical Manufacturer Unit / Sub-Unit Electrical Ratings Tank Capacity
5 kVA Generator Eisemann / Endress Command Squad, Supply Unit 5.0 kVA (4.0 kW) / 230 V / 400 V (7.2 A/phase) approx. 11 L Gasoline
8 / 13 kVA Generator Eisemann DIN 14685 Rescue Group 8.0 / 13.0 kVA (6.4 / 10.4 kW) (18.7 A/phase) approx. 20 L Gasoline
50 kVA Power Unit Polyma / Kirsch / AVS Emergency Supply Unit 50.0 kVA (40.0 kW) / 400 V (72.2 A/phase) approx. 120 L Diesel
175 / 200 kVA Unit Polyma / Bredenoord Electrical Power, Water Damage 175 / 200 kVA (140 / 160 kW) (288 A/phase) approx. 350–500 L Diesel

Configurable Parameters:

Parameter Description Typical Standard Value
Designation Tactical call sign or name 50 kVA Generator (Supply Unit)
Apparent Power (\(S_n\)) Maximum total apparent power e.g. 50.0 kVA
Active Power (\(P_n\)) Available active power (\(\cos\varphi = 0.8\)) e.g. 40.0 kW
Nominal Voltage (\(U_n\)) Output voltage 400 V 3-phase / 230 V 1-phase
Max Current per Phase Calculated maximum current per winding e.g. 72.2 A at 50 kVA
Fuel Type Diesel or Gasoline Diesel
Tank Volume Internal tank capacity e.g. 120 Liters

⏱️ Dual Operating Hours Tracking

For accurate accounting and strict adherence to inspection intervals, the app combines two tracking methods:

  1. Automatic Timer:
  2. As soon as a generator is set to “Operating” in the app, an internal background timer increments operating hours automatically.
  3. Even during temporary device disconnections, the counter continues accurately based on synchronized server timestamps.
  4. Manual Adjustment:
  5. During shift changes, maintenance, or unit replacement, operators can align the software counter directly with the mechanical hour meter on the generator.
  6. Discrepancies are logged in the audit trail with a justification.

🔧 Maintenance Intervals & Early Warnings

Power generators are subject to defined maintenance and inspection intervals according to manufacturer guidelines and standards:

Interval (Operating Hours) Scope of Service Typical Actions
50 h Initial service / break-in oil change Initial oil change, bolt tightness check
100 h Routine maintenance Level 1 Engine oil level check, spark plug / fuel pre-filter cleaning, RCD test
250 h Major inspection Level 2 Engine oil & filter replacement, air filter service, valve clearance check
500 h Overhaul Level 3 V-belt tensioning, fuel injector testing, insulation measurement (DGUV V3)

Color-Coded Due Date Indicators

  • 🟡 Yellow Warning: When a generator reaches 10 hours before the interval, the app displays a maintenance reminder in the generator menu.
  • 🔴 Red Overdue Alarm: If the maintenance interval is exceeded, the generator is flagged on the Dashboard to prevent field failures.

⛽ Digital Refueling Records (RefuelEvent)

For auditable documentation for cost authorities, the refueling dialog captures all essential metrics:

  • Slider: Fast, glove-friendly input of fuel level in percentage (%) and liters (L).
  • Required Field “Performed By”: Name and call sign of the operator.
  • Consumption Calculation: Automatic subtraction of pre- and post-refueling levels to calculate effective liters added.

📈 5-Point Fuel Consumption Curve

Unlike simplified flat rates, the Stromnetz Pro uses a precise 5-point fuel consumption curve (l/h at various load levels). The engine linearly interpolates between support points:

xychart-beta
    title "5-Point Consumption Curve (Liters / Hour per Load Level)"
    x-axis ["0% (Idle)", "25% Load", "50% Load", "75% Load", "100% (Full)"]
    y-axis "Fuel Consumption (l/h)" 0 --> 16
    bar [2.1, 4.5, 7.8, 11.2, 15.0]
    line [2.1, 4.5, 7.8, 11.2, 15.0]

Advantage of Consumption Curves

Because generators consume significantly less fuel at partial loads (e.g. at night feeding light loads) than at full load, the Stromnetz Pro provides realistic predictions for the next refueling window and avoids unexpected fuel depletion.


🔘 Generator States

A power generator can assume the following states:

  • 🟢 Online (Operating): The unit actively feeds into the grid. All connected consumers are included in load calculations.
  • ⚪ Offline (Standby / Fault): The generator is off. Connected branches are marked as unpowered.
  • 🔴 Overloaded: Connected load exceeds rated capacity (> 100%) or an individual phase exceeds maximum phase current. The app signals this acoustically and visually with a red warning banner.

⚖️ Phase Monitoring & Phase Unbalance (30% Threshold)

In the detail view of each generator, the app visualizes line current loads across all three phases:

flowchart LR
    subgraph Generator ["50 kVA Unit (Max 72.2 A / Phase)"]
        L1["L1: 62.0 A (86%)"]
        L2["L2: 58.0 A (80%)"]
        L3["L3: 65.0 A (90%)"]
    end
    Generator --> Check{"Unbalance Check<br>Max Diff: 7.0 A (9.7%)"}
    Check -- "Diff ≤ 30%" --> OK["🟢 Phases balanced"]
    Check -- "Diff > 30%" --> ALARM["🔴 WARNING: Unbalance > 30%!<br>Risk of rotor overheating & neutral shift"]
    style OK fill:#dcfce7,stroke:#10b981,stroke-width:2px;
    style ALARM fill:#fee2e2,stroke:#ef4444,stroke-width:2px;
  • Phase Load Bars L1, L2, L3: Shows RMS current in Amperes (A) and winding load percentage.
  • 30% Phase Unbalance Limit (DIN VDE 0100 & Field Standards):
    If the difference between the most heavily and least heavily loaded phases exceeds 30% of rated capacity, a visual and acoustic unbalance alarm is triggered immediately.
  • Hazards of Uncorrected Phase Unbalance:
  • Impermissible heating of generator rotor windings (negative-sequence eddy currents).
  • Dangerous neutral point shift, causing overvoltages up to nearly 400 V on lightly loaded phases and destroying connected electronic gear.

⚡ Staging Optimizer & Wet-Stacking Prevention (GeneratorStagingOptimizer)

During deployments with multiple generators or fluctuating loads, the Staging Optimizer continuously evaluates generator efficiency:

  • Wet-Stacking Prevention (< 30% Load):
  • When a Diesel generator runs below 30% load, the app flags wet-stacking risk (unburned fuel accumulation in exhaust systems and carbon buildup).
  • The system advises consolidating loads or downsizing to a smaller generator.
  • Multi-Generator Staging Recommendations:
  • If fewer online generators could carry the entire grid demand within the optimal load window (50–85%), the app emits a staging recommendation to shut down excess units, cutting fuel burn and engine wear.