Chapter 6: Fuel Logistics & Hour Tracking¶
In extended disaster operations (e.g. multi-day flood response or power grid outages), continuous fuel replenishment for generators is a core logistical challenge. A generator running dry can suffer fuel injection damage and shut down vital emergency facilities.
⛽ Fuel Consumption Math (FuelMath) & Runtime Forecast¶
The Stromnetz Pro correlates live electrical grid load with each generator's 5-point fuel consumption curve using FuelMath:
- Non-Linear Load Dependency: Combustion engines consume a minimum baseline fuel amount at idle (0%) to overcome friction and excitation. Specific consumption increases non-linearly with electrical load.
- Piecewise Linear Interpolation:
FuelMathdynamically interpolates instant consumption \(B_{\text{Load}}\) (in l/h) between support points (0%, 25%, 50%, 75%, 100%).
Exact Runtime Forecast (\(t\)):¶
Remaining runtime in hours and minutes is calculated from usable tank volume divided by current fuel consumption:
flowchart LR
Load["⚡ Generator Load (kW)<br>e.g. 34 kW (68%)"] --> Interp["FuelMath Interpolation<br>Instant Fuel B_Load: 10.4 l/h"]
Tank["⛽ Fuel Level V_Remaining<br>e.g. 65 Liters"] --> Calc["Runtime Forecast<br>t = 65 l / 10.4 l/h = 6h 15m"]
Interp --> Calc
Calc --> Status{"Check Fuel Reserve"}
Status -- "Tank > 20% & t > 1h" --> OK["🟢 Normal Operation"]
Status -- "Tank ≤ 20% or t ≤ 1h" --> WARN["🟡 20% Reserve Warning: Request fuel!"]
Status -- "Tank ≤ 5% or t ≤ 15 min" --> CRIT["🔴 Acoustic Alarm: Outage imminent!"]
style OK fill:#dcfce7,stroke:#10b981;
style WARN fill:#fef3c7,stroke:#f59e0b,stroke-width:2px;
style CRIT fill:#fee2e2,stroke:#ef4444,stroke-width:2px;
- Automatic 20% Reserve Warning: When tank level drops below 20% or remaining runtime falls under 1 hour, a yellow warning banner and chime trigger on the Dashboard.
- Critical Alarm (< 5%): Signals acute shutdown risk, preventing air-locking in diesel fuel lines.
🛢️ Jerrycan & Fuel Tanker Logistics¶
During major incidents, fuel is supplied via mobile containers:
- Standard Jerrycans (20 L NATO Standard):
- Track available and consumed cans in the material pool.
- Rapid logging of fuel draws (e.g. 2 cans à 20 L = 40 L).
- Mobile Fuel Bowsers & Tankers:
- Record bulk refuels from mobile tanks (1,000 L IBCs, fuel trailers, bowsers).
- Material Pool Integration:
- Every refuel deducts fuel volume automatically from total logistical stock.
📝 Logging Refuelings (RefuelEvent)¶
Fuel additions can be recorded with a few taps:
- Open Fuel Logistics in the drawer menu.
- Select the generator and tap “+ Record Refueling”.
- Fill in the form:
- Amount (Liters): e.g. 40 Liters (2 cans à 20 L).
- Performed By: Required name or call sign of operator.
- Post-Refuel Level: Convenient slider input in percent and liters.
- Tap “Save”.
Tank level updates immediately, and pre-/post-refueling values are logged with timestamps in mission reports.
⏱️ Operating Hours Tracking¶
Power generators require strict adherence to inspection intervals:
- Reading Hour Meters: During shift handovers or inspections, operators align software counters with mechanical hour meters on the engine.
- Dynamic Service Intervals: The app monitors service thresholds (50 h, 100 h, 250 h, 500 h) and alerts 10 hours before due dates.
- Audit Trail for Reimbursements: The complete log serves as official proof for operational cost recovery with requesting authorities.
⏱️ Shift Demand Calculator & Tactical Reserve (ShiftFuelCalculator)¶
To proactively prevent supply bottlenecks during prolonged deployments, the app computes forecasted fuel demands for standard shifts (8 h, 12 h, 24 h):
- Tactical Buffer: Automatically includes a 20% tactical reserve to cushion against surge currents or supply delays.
- Automated Logistics Recommendation:
- When forecasted shift consumption exceeds 150 liters, the app automatically recommends ordering a mobile fuel bowser or bulk fuel container.
- For lower demands, the app computes the exact number of required standard 20 L jerrycans.