Zum Inhalt

Chapter 6: Fuel Logistics & Hour Tracking

In extended disaster operations (e.g. multi-day flood response or power grid outages), continuous fuel replenishment for generators is a core logistical challenge. A generator running dry can suffer fuel injection damage and shut down vital emergency facilities.


⛽ Fuel Consumption Math (FuelMath) & Runtime Forecast

The Stromnetz Pro correlates live electrical grid load with each generator's 5-point fuel consumption curve using FuelMath:

  • Non-Linear Load Dependency: Combustion engines consume a minimum baseline fuel amount at idle (0%) to overcome friction and excitation. Specific consumption increases non-linearly with electrical load.
  • Piecewise Linear Interpolation: FuelMath dynamically interpolates instant consumption \(B_{\text{Load}}\) (in l/h) between support points (0%, 25%, 50%, 75%, 100%).

Exact Runtime Forecast (\(t\)):

Remaining runtime in hours and minutes is calculated from usable tank volume divided by current fuel consumption:

\[t = \frac{V_{\text{Remaining}}}{B_{\text{Load}}}\]
flowchart LR
    Load["⚡ Generator Load (kW)<br>e.g. 34 kW (68%)"] --> Interp["FuelMath Interpolation<br>Instant Fuel B_Load: 10.4 l/h"]
    Tank["⛽ Fuel Level V_Remaining<br>e.g. 65 Liters"] --> Calc["Runtime Forecast<br>t = 65 l / 10.4 l/h = 6h 15m"]
    Interp --> Calc

    Calc --> Status{"Check Fuel Reserve"}
    Status -- "Tank > 20% & t > 1h" --> OK["🟢 Normal Operation"]
    Status -- "Tank ≤ 20% or t ≤ 1h" --> WARN["🟡 20% Reserve Warning: Request fuel!"]
    Status -- "Tank ≤ 5% or t ≤ 15 min" --> CRIT["🔴 Acoustic Alarm: Outage imminent!"]

    style OK fill:#dcfce7,stroke:#10b981;
    style WARN fill:#fef3c7,stroke:#f59e0b,stroke-width:2px;
    style CRIT fill:#fee2e2,stroke:#ef4444,stroke-width:2px;
  • Automatic 20% Reserve Warning: When tank level drops below 20% or remaining runtime falls under 1 hour, a yellow warning banner and chime trigger on the Dashboard.
  • Critical Alarm (< 5%): Signals acute shutdown risk, preventing air-locking in diesel fuel lines.

🛢️ Jerrycan & Fuel Tanker Logistics

During major incidents, fuel is supplied via mobile containers:

  • Standard Jerrycans (20 L NATO Standard):
  • Track available and consumed cans in the material pool.
  • Rapid logging of fuel draws (e.g. 2 cans à 20 L = 40 L).
  • Mobile Fuel Bowsers & Tankers:
  • Record bulk refuels from mobile tanks (1,000 L IBCs, fuel trailers, bowsers).
  • Material Pool Integration:
  • Every refuel deducts fuel volume automatically from total logistical stock.

📝 Logging Refuelings (RefuelEvent)

Fuel additions can be recorded with a few taps:

  1. Open Fuel Logistics in the drawer menu.
  2. Select the generator and tap “+ Record Refueling”.
  3. Fill in the form:
  4. Amount (Liters): e.g. 40 Liters (2 cans à 20 L).
  5. Performed By: Required name or call sign of operator.
  6. Post-Refuel Level: Convenient slider input in percent and liters.
  7. Tap “Save”.

Tank level updates immediately, and pre-/post-refueling values are logged with timestamps in mission reports.


⏱️ Operating Hours Tracking

Power generators require strict adherence to inspection intervals:

  • Reading Hour Meters: During shift handovers or inspections, operators align software counters with mechanical hour meters on the engine.
  • Dynamic Service Intervals: The app monitors service thresholds (50 h, 100 h, 250 h, 500 h) and alerts 10 hours before due dates.
  • Audit Trail for Reimbursements: The complete log serves as official proof for operational cost recovery with requesting authorities.

⏱️ Shift Demand Calculator & Tactical Reserve (ShiftFuelCalculator)

To proactively prevent supply bottlenecks during prolonged deployments, the app computes forecasted fuel demands for standard shifts (8 h, 12 h, 24 h):

  • Tactical Buffer: Automatically includes a 20% tactical reserve to cushion against surge currents or supply delays.
  • Automated Logistics Recommendation:
  • When forecasted shift consumption exceeds 150 liters, the app automatically recommends ordering a mobile fuel bowser or bulk fuel container.
  • For lower demands, the app computes the exact number of required standard 20 L jerrycans.