Appendix A: Machinist Cheat Sheet (Quick Reference)¶
This cheat sheet summarizes key metrics, VDE limit values, conversion formulas, and reference tables. Ideal for printing, laminating, and attaching to generators or command vehicles.
⚡ Core Limits at a Glance¶
| Parameter | Limit / Reference | Standard / Rule | Consequence if Exceeded |
|---|---|---|---|
| Max Voltage Drop (\(\Delta U\)) | \(\le 3.0\%\) | DIN VDE 0100-520 | Cable fire risk, equipment malfunction, pump overheating. |
| Max Voltage Drop in Volts | \(\le 6.9\text{ V}\) (at 230 V) \(\le 12.0\text{ V}\) (at 400 V) |
DIN VDE 0100 | Undervoltage on appliances. |
| Phase Unbalance Tolerance | \(\le 30\%\) difference | Manufacturer / Field Standard | Neutral shift, generator rotor overheating. |
| Fuel Reserve Warning | \(< 20\%\) or \(< 1\text{ h}\) remaining | Field Practice | Generator running dry, diesel bleeding required. |
| Power Factor (\(\cos\varphi\)) | 0.8 (standard default) | DIN 6280 / Nameplate | Conversion from Apparent (\(S\) in kVA) to Active Power (\(P\) in kW). |
📐 Electrical Formula Reference¶
1. Calculating Current Draw (\(I\) in Amperes)¶
- 1-Phase AC (230 V):
I = P / (U · cos φ) = P / (230 V · cos φ) - 3-Phase AC (400 V symmetric):
I = P / (√3 · U · cos φ) = P / (1.732 · 400 V · cos φ)
2. Apparent Power & Active Power¶
P [kW] = S [kVA] · cos φ ⟷ S [kVA] = P [kW] / cos φ
3. Voltage Drop Calculation (\(\Delta U\))¶
Copper electrical conductivity: \(\kappa = 56\,\frac{\text{m}}{\Omega \cdot \text{mm}^2}\)
- 1-Phase AC (230 V):
$\(\Delta U [\%] = \frac{2 \cdot L \cdot I \cdot \cos\varphi}{\kappa \cdot A \cdot 230\,\text{V}} \cdot 100\% \approx \frac{L \cdot I \cdot \cos\varphi}{64.4 \cdot A}\)$ -
3-Phase AC (400 V symmetric):
$\(\Delta U [\%] = \frac{\sqrt{3} \cdot L \cdot I \cdot \cos\varphi}{\kappa \cdot A \cdot 400\,\text{V}} \cdot 100\% \approx \frac{L \cdot I \cdot \cos\varphi}{129.3 \cdot A}\)$ -
\(L\) = One-way cable length in meters (m)
- \(I\) = RMS current in Amperes (A)
- \(A\) = Cross-section in \(\text{mm}^2\)
- \(\cos\varphi\) = Power factor
4. Fuel Runtime Forecast (FuelMath)¶
- \(t\) = Remaining runtime in hours
- \(V_{\text{Remaining}}\) = Current tank volume in liters
- \(B_{\text{Load}}\) = Fuel consumption rate at active load in l/h (from 5-point curve)
📏 Reference Table for Cable Cross-Sections & Max Lengths¶
Permissible cable lengths for copper conductors (Type H07RN-F) at rated current and \(\le 3.0\%\) voltage drop:
| Cross-Section | Connector Type | Fusing / Rated Current | Max Recommended Length (\(\Delta U \le 3.0\%\)) | Typical Field Use |
|---|---|---|---|---|
| 1.5 mm² | Schuko | 10 A (continuous) | approx. 25 m | LED lighting, small tools |
| 1.5 mm² | Schuko | 16 A (full load) | approx. 16 m | Short extension leads only! |
| 2.5 mm² | CEE 16A / Schuko | 16 A | approx. 27 m | Standard for Schuko & CEE 16A |
| 4.0 mm² | CEE 32A | 25 A | approx. 35 m | Sub-distribution feeders |
| 6.0 mm² | CEE 32A | 32 A | approx. 38 m | Standard CEE 32A feeder |
| 10.0 mm² | CEE 63A | 50 A | approx. 42 m | Main distribution runs |
| 16.0 mm² | CEE 63A | 63 A | approx. 55 m | Heavy pumps / power units |
| 25.0 mm² | CEE 125A / Powerlock | 80 A | approx. 68 m | 50 kVA generator feeder |
| 35.0 mm² | CEE 125A / Powerlock | 100 A | approx. 75 m | Main heavy cables |
| 50.0 mm² | Powerlock | 125 A | approx. 85 m | Heavy-duty power supply |
| 70.0 mm² | Powerlock / Single core | 160 A | approx. 95 m | 175 kVA generator feeder |
| 95.0 mm² | Powerlock / Single core | 200 A | approx. 110 m | Heavy 200 kVA generator feeder |
⚠️ Coiled Cable Reels: Thermal Derating¶
Always fully uncoil cable drums!
Coiled cable reels act as heat traps. Capacity drops to approx. 35% of rated value:
- Coiled: Maximum approx. 1,000 W (4.3 A) continuous load!
- Fully Uncoiled: Maximum approx. 3,500 W (16 A) continuous load.
flowchart LR
A["Coiled Cable Reel<br>Max 1,000 Watts (4.3 A)"] -- "Uncoil completely" --> B["Uncoiled Cable Reel<br>Max 3,500 Watts (16 A)"]
style A fill:#fee2e2,stroke:#ef4444,stroke-width:2px;
style B fill:#dcfce7,stroke:#10b981,stroke-width:2px;
🔄 Inrush Currents of Typical Field Appliances¶
Motors and floodlights draw multiples of rated current at startup:
| Appliance Type | Inrush Factor | Operational Consideration |
|---|---|---|
| Submersible Trash Pumps | 3× to 5× Rated Current | Plan generators with double reserve; use star-delta soft starters. |
| Halogen Floodlights (1000 W / 2000 W) | 8× to 10× Rated Current | Cold filaments have low resistance. Switch floodlights on sequentially! |
| LED Balloon Lights | 1.2× to 1.5× Rated Current | Uncritical continuous draw; microsecond capacitive switching spikes. |
| Power Tools & Angle Grinders | 2× to 4× Rated Current | Soft starters significantly reduce generator strain. |
🚦 Color Coding System¶
1. Technical Grid Alarms & Limits¶
| Status Color | Technical Meaning | Required Action |
|---|---|---|
| 🟢 Green (OK) | Parameters optimal. \(\Delta U \le 2.5\%\), generator load \(< 80\%\), phase balance OK. | Normal operation; no action needed. |
| 🟡 Yellow (Warning) | Nearing limit. \(3.0\% < \Delta U \le 5.0\%\), fuel \(< 20\%\), unbalance \(> 25\%\). | Prepare action: Request fuel, shorten cables, or re-balance load. |
| 🔴 Red (Critical) | Limit exceeded! \(\Delta U > 5.0\%\), unbalance \(> 30\%\), overload, fuel \(< 5\%\). | Immediate Intervention: Shed load, increase cable cross-section, swap phases! |
2. Consumer Priority Levels & Load Shedding¶
| Priority | Symbol & Color | Category | Behavior on Generator Overload |
|---|---|---|---|
| 1 | 🚨 Red | VITAL (Life-Critical) | Must never be shed (Medical tent, respirators). |
| 2 | 🔶 Orange | ESSENTIAL | High priority (Command post, heavy pumps). |
| 3 | 🔷 Blue | OPERATIONAL | Standard operation (Workshop, charging station). |
| 4 | ⚪ Gray | SHEDDABLE | First shedding stage: Coffee machines, space heaters. |
Load Shedding Cascade: ⚪ SHEDDABLE \(\longrightarrow\) 🔷 OPERATIONAL \(\longrightarrow\) 🔶 ESSENTIAL \(\longrightarrow\) 🚨 VITAL.
🎙️ Voice Command Quick Reference & Wake-Words ("Hey Stromapp")¶
Hands-Free Voice Control provides contactless grid operations at the generator without removing gloves:
1. Supported Wake Phrases (Wake-Words)¶
- App Call Signs: "Hey Stromapp", "Hallo Stromapp", "Stromapp"
- Voice Call Signs: "Hey Stromnetz", "Hallo Stromnetz", "Sprachbefehl starten", "Befehl starten"
- Standard Commands: "Sprachbefehl starten", "Sprachsteuerung starten", "Startbefehl starten", "Startbefehl"
2. Typical One-Shot Commands (Single Utterance)¶
| Operational Task | Example Speech Command (One-Shot) |
|---|---|
| Set Fuel Level | "Hey Stromapp, generator 1 fuel level 70%" (or "... 45 liters") |
| Connect Device | "Hey Stromapp, connect Halogen 1000W to generator 1 on phase 2" |
| Switch Phase | "Hey Stromapp, switch pump 1 to phase 3" |
| Disconnect Device | "Hey Stromapp, disconnect pump 2" |
| Create Mission | "Hey Stromapp, new mission Disaster Dresden" |
| Log Operational Note | "Hey Stromapp, note: cable drum 1 replaced due to overheating" |
| Export Report | "Hey Stromapp, create mission report" |
💡 Field Tip: Recognition is acknowledged with a tone cue (
Beep) and vibration. Follow-up dialogs can be answered by voice ("Yes", "Confirm", "Execute" / "Ja", "Bestätigen") or option numbers ("1", "2").