Chapter 4: Consumers, Cables & Distributors

A temporary power grid relies on its cable runs and connected appliances – from submersible pumps and floodlight masts to command and medical tents.


🔌 Adding & Managing Consumers

Tap Consumers in the menu and select “+ Add Consumer”:

1. Phase Type & Rating

  • 1-Phase AC (230 V): Select the specific phase: Phase 1 (L1), Phase 2 (L2), or Phase 3 (L3). Tip: Distributing single-phase heavy loads (e.g. tent heaters or hotplates) across different phases balances the grid perfectly!
  • 3-Phase AC (400 V): For motors, heavy pumps, or light towers with 3-phase connections. Load is balanced evenly across all three phases.

2. Dual Load Input (Amperes vs. Kilowatts) & Power Factor

The consumer dialog features a Unit Toggle:

  • Input in Amperes (A): Direct entry of rated current read from the appliance nameplate.
  • Input in Kilowatts (kW): Entry of electrical active power.
  • Automatic Conversion: The app automatically converts taking voltage and power factor \(\cos\varphi\) into account:
  • 1-Phase AC (230 V):
    $\(P = U \cdot I \cdot \cos\varphi \quad \Longleftrightarrow \quad I = \frac{P}{U \cdot \cos\varphi}\)$
  • 3-Phase AC (400 V):
    $\(P = \sqrt{3} \cdot U \cdot I \cdot \cos\varphi \quad \Longleftrightarrow \quad I = \frac{P}{\sqrt{3} \cdot U \cdot \cos\varphi}\)$

3. Load Stages & Inrush Currents (startupFactor)

  • Multi-Stage Consumers: Appliances like space heaters or star-delta starting pumps feature multiple power levels. You can configure stages and switch between partial and full load with one tap during operation.
  • Inrush Current Factor (startupFactor): Inductive loads (e.g. submersible pumps, compressors, desiccant dehumidifiers) draw multiples of rated current briefly during startup.
  • Assign the appropriate inrush factor (typically 2.5× to 6.0×).
  • The calculation engine verifies in advance whether the feeding generator has sufficient dynamic capacity to handle startup without voltage dips.

4. Four Priority Classes for Tactical Load Shedding

Each consumer is assigned one of four priority levels:

Priority Class Color Code Tactical Significance Example Appliances
VITAL / LIFE-CRITICAL 🚨 Red Uninterruptible supply; must never be shed. Medical tent, respirators, dike protection pumps
ESSENTIAL 🔶 Orange Primary mission fulfillment; high priority. Command post, radio repeaters, main floodlights
OPERATIONAL 🔷 Blue Standard operational support. Workshop tent, battery charging stations, general lighting
SHEDDABLE ⚪ Gray Convenience and non-essential loads. Coffee machines, space heaters, comfort AC

Tactical Load Shedding Cascade

If generator overload threatens (> 100% rated load or winding overheating), the Stromnetz Pro recommends stepwise load shedding strictly from non-essential to vital:
⚪ SHEDDABLE \(\longrightarrow\) 🔷 OPERATIONAL \(\longrightarrow\) 🔶 ESSENTIAL \(\longrightarrow\) 🚨 VITAL.


🧵 Cables & Cable Drums

Cables are the arteries of the grid. For accurate voltage drop and safety calculations, the app records three key parameters:

flowchart TD
    Gen["⚡ Power Generator"] -->|"Cable C1: 50m / 6.0 mm²"| V1["🔀 Main Distributor V1<br>(CEE 32A)"]
    V1 -->|"Cable C2: 25m / 2.5 mm² (uncoiled)"| V2["Distribution Box V2<br>(3x Schuko)"]
    V1 -->|"Cable C3: 25m (coiled ⚠️)<br>Derating: max 1000 W"| Load["💡 Floodlight 1000 W"]

    style Gen fill:#dbeafe,stroke:#003399,stroke-width:2px;
    style V1 fill:#f1f5f9,stroke:#475569;
    style V2 fill:#f8fafc,stroke:#94a3b8;
    style Load fill:#fef3c7,stroke:#f59e0b;

1. Standardized Cable Cross-Sections

Select the actual cross-section of the cable used (Type H07RN-F):

Cross-Section Connector Type Typical Fusing Max Continuous Current Typical Field Usage
1.5 mm² Schuko 10 A / 16 A 16 A (uncoiled) Short extensions, LED lights
2.5 mm² CEE 16A / Schuko 16 A 16 A Standard cable reel (400 V & 230 V)
4.0 mm² CEE 32A 25 A 25 A Medium distribution feeds
6.0 mm² CEE 32A 32 A 32 A Standard 32A distribution runs
10.0 mm² CEE 63A 50 A 50 A Main supply runs for tent camps
16.0 mm² CEE 63A 63 A 63 A Standard CEE 63A runs
25.0 mm² CEE 125A / Powerlock 80 A 80 A 50 kVA generator grid feed
35.0 mm² CEE 125A / Powerlock 100 A 100 A Main cables for large generators
50.0 mm² Powerlock 125 A 125 A Heavy-duty supply runs
70.0 mm² Single core / Powerlock 160 A 160 A 175 kVA generator feeder
95.0 mm² Single core / Powerlock 200 A–250 A 250 A Heavy 200 kVA generator feeder

2. Cable Length (L in Meters)

Enter the actual length of the line (e.g. 25 m reel, 50 m line).

3. State: Uncoiled vs. Coiled (Thermal Derating) ⚠️

Cable Reel State Max Current Capacity Max Power at 230 V Fire Hazard
Fully Uncoiled 16 A up to 3,500 W 🟢 Heat dissipates fully into ambient air.
Coiled (Heat Trap) approx. 4.3 A max 1,000 W 🔴 Insulation melting, fire & short circuit hazard!

Cable Fire Hazard on Coiled Reels!

Coiled cable reels cannot dissipate generated Joule heat to ambient air. The insulation melts, threatening short circuits or fires.

  • When marking a cable as “Coiled”, the Stromnetz Pro automatically reduces maximum current capacity by a safety factor (derating factor approx. 0.35) and warns of overheating even at modest currents!

🔀 Distributors & Configurable Socket Ports

Distributors split incoming power runs into multiple branch outputs:

  • Distribution Boxes (16A / 32A): e.g. CEE 16A inlet to 3x Schuko outlets.
  • Site Distribution Panels (63A / 32A / 16A): For supplying entire tent streets or pumping stations with internal RCDs and circuit breakers.
  • Configurable Port Outlets (outputsJson): Freely configure individual socket types (Schuko, CEE 16A/32A/63A/125A) for distributors and multi-socket cable reels, enabling precise port routing and automated socket-level overload checks.

🌡️ Cable Bundling (DIN VDE 0298-4) & Ambient Temperature Derating

When cables are bundled together or deployed in high ambient temperatures, thermal dissipation drops significantly:

  • Bundling Derating (DIN VDE 0298-4): The app applies reduction factors for bundled cables (e.g. 0.80 for 2 cables, 0.70 for 3, 0.60 for 6 or more).
  • Ambient Temperature: For ambient temperatures exceeding 30 °C (direct sunlight or near generator exhausts), thermal current carrying capacity is reduced per VDE standards.

📐 Normative Cable Sizing Assistant (DIN VDE 0298-4)

To support incident commanders and electricians during network planning, the app features an integrated Cable Sizing Assistant:

  1. Minimum Cross-Section Calculation: Determines the required conductor cross-section based on design current, installation type, and mission ambient temperature per DIN VDE 0298-4.
  2. Voltage Drop Boundary Check (\(\Delta U \le 3.0\%\)): Verifies the planned cable run length and automatically suggests stepping up to a larger cross-section (e.g. \(2.5\,\text{mm}^2 \to 4.0\,\text{mm}^2\) or \(6.0\,\text{mm}^2\)) if the 3.0% threshold is breached.
  3. Maximum Permissible Cable Length: Directly displays the maximum distance a given cable cross-section can span under full load before unacceptable voltage drop occurs.