Appendix B: Technical & Electrical Glossary

This glossary explains key terms from emergency management, electrical engineering under DIN VDE, and system architecture of Stromnetz Pro.


A

  • AES-256 Column Encryption: Cryptographic protection of sensitive database fields (commanders, exact addresses, notes) in the local SQLite/Room database using 256-bit keys.
  • Apparent Power (\(S\) in kVA): Vector sum of active power \(P\) and reactive power \(Q\) (\(S = \sqrt{P^2 + Q^2}\)). Represents total power drawn from the generator.
  • Active Power (\(P\) in kW): Electrical power converted into real work, heat, or light (\(P = S \cdot \cos\varphi\)).
  • Audit Log: Chronological log of all safety-critical switching actions, alarms, shift changes, and pairings in the app.

C

  • CEE Connectors: Internationally standardized industrial connectors:
  • CEE 16A (Red): 400 V 3-phase AC up to 11 kW.
  • CEE 32A (Red): 400 V 3-phase AC up to 22 kW.
  • CEE 63A (Red): 400 V 3-phase AC up to 44 kW.
  • CEE 16A (Blue): 230 V single-phase AC.
  • Cosine Phi (\(\cos\varphi\) / Power Factor): Ratio of active power \(P\) to apparent power \(S\). For 3-phase generators and motors, calculated with default \(\cos\varphi = 0.8\).

D

  • Delta Update (Incremental Sync): Data sync technique in P2P mesh exchanging only modified database records to conserve battery and radio bandwidth.
  • Derating: Mathematical reduction of cable current capacity under adverse conditions (e.g. heat trapping in coiled drums).
  • DGUV Regulation 3: Accident prevention regulation for electrical systems and equipment in operations.
  • DIN VDE 0100-520: Standard governing low-voltage electrical installations; specifies maximum permissible voltage drop of 3.0%.

E

  • ECDH (Elliptic Curve Diffie-Hellman): Key exchange protocol (secp256r1) allowing two smartphones in the field to establish an AES-256 session key without internet.

H

  • H07RN-F: Standard heavy-duty rubber-sheathed flexible cable. Standard field cable due to mechanical durability, oil, and weather resistance.
  • Gloves Mode: Accessibility mode with enlarged touch targets (at least 64 dp) and wide spacing for heavy protective gloves (DIN EN 388).
  • Hands-Free Voice Control: 100% offline-capable voice assistant enabling touchless control (grid topology, phase switching, refueling, reports) around generators with work gloves.

I

  • Inrush Current: Brief initial current drawn by electric motors (e.g. pumps) at startup, up to 3 to 6 times rated current.
  • InventoryManager: Internal engine reconciling target vehicle equipment lists with active field deployments.
  • IT Grid: Isolated grid without direct grounding of active conductors, typical for portable generators with insulation monitoring.

L

  • Last-Write-Wins (LWW): Conflict resolution mechanism merging concurrent offline edits based on timestamps.
  • Load Curve: Graphical representation of active/apparent power draw over mission duration in PDF reports.

M

  • MBTiles: Open file format for offline map tile archives. Enables offline tactical mapping without cellular network.

N

  • Nearby Connections: Framework enabling wireless ad-hoc mesh networks via Bluetooth Low Energy (BLE) and Wi-Fi Direct without external routers.
  • Neutral Point Shift: Dangerous voltage shift in 3-phase networks caused by extreme unbalance or broken neutral conductors. Single-phase loads can receive overvoltage (up to 400 V) and suffer damage!

P

  • P2P Mesh: Decentralized radio network between smartphones/tablets without cell towers or internet.
  • Phase Unbalance: Unequal current loading across 3-phase generator windings L1, L2, and L3. Differences exceeding 30% risk rotor overheating.

R

  • RCD (Residual Current Device): Safety device disconnecting power within milliseconds upon detecting leakage currents to ground (typically 30 mA).
  • Reactive Power (\(Q\) in kvar): Power oscillating between generator and load to establish magnetic fields in motors or transformers without performing net work.

S

  • Safe Auto-Approve: Intelligent mesh policy auto-approving non-critical actions while requiring manual commander sign-off for actions risking overload or voltage drop.
  • Single Line Diagram (SLD): Standardized single-line schematic diagram (DIN EN 60617) representing the entire temporary power grid for plotters and command staff.
  • Stealth Mode: Security function disabling all wireless interfaces (BLE/Wi-Fi) for radio-silent operations.

T

  • TN-S Grid: Grid grounding scheme with separate protective earth (PE) and neutral (N) conductors and grounded neutral point at generator. Standard for large generator net feeds.

V

  • Voltage Drop (\(\Delta U\)): Voltage loss between generator and consumer caused by cable resistance. Maximum allowed is 3.0%.

W

  • Wake-Word: Trigger phrase such as "Hey Stromapp", "Hallo Stromapp", or "Sprachbefehl starten" waking continuous foreground voice recognition to receive commands.